CL-206-E H2S, Temperature and Humidity Data Logger, RS-485 and PoE Ethernet
H2S, temperature, humidity and dew point data logger with RS-485 and PoE Ethernet. Stores up to 450,000 time-stamped records and drives a relay output for alarms or IAQ device control.
- Records H2S, temperature, humidity and dew point with date and time stamps
- Stores up to 450,000 downloadable records
- Supports DCON, Modbus RTU, Modbus TCP and MQTT
- RS-485 and Ethernet interfaces with PoE or +12 ~ +48 VDC terminal block power
- Relay output (1 x Form A, SPST) for alarm or IAQ device control
- H2S measurement to 100 ppm, electrochemical sensor, 1 ppm resolution
424,00 € pro Stück
| 1–9 Stück | 424,00 € | |
|---|---|---|
| 10–30 Stück | 412,00 € | −3 % |
| ab 31 Stück | 403,00 € | −5 % |
Produktinformationen "CL-206-E H2S, Temperature and Humidity Data Logger, RS-485 and PoE Ethernet"
CL-206-E CR is a data logger module for monitoring hydrogen sulphide alongside temperature, relative humidity and dew point. Each reading is stored with date and time stamps, so the logged history can be downloaded and reviewed later, while live values can be polled over the network.
The module offers both RS-485 and Ethernet connectivity and can be powered over PoE or from a +12 ~ +48 VDC terminal block. It speaks DCON, Modbus RTU, Modbus TCP and MQTT, which makes it straightforward to bring into an existing HMI, SCADA or IoT platform. A single Form A relay output can be used for alarm signalling or to control IAQ equipment.
Typical deployments include building and energy management, warehouse storage, food and beverage HACCP records, and the transport of food or pharmaceuticals, where a documented environmental record is required. The module is intended for indoor installation, mounted on a ceiling or wall.
Applications
- Transportation of food or pharmaceuticals
- Food and beverage industry (HACCP)
- Blood stations and pharmacies
- Building and energy management
- Warehouse management
- Museums, archives and galleries
| Product type: | Data logger module |
|---|---|
| Interface: | Ethernet, RS-485 |
| Protocol: | DCON, Modbus RTU, Modbus TCP, MQTT |
| Relay outputs: | 1 x Form A |
| Ports: | 2 |
| PoE: | Yes |
| Power input: | +12 ~ +48 VDC |
| Operating temperature: | 0 ~ 50 °C |
| Mounting: | Ceiling/Wall |
Technische Daten
| System | |
|---|---|
| Alarm | H2S/RH/Temperature |
| Real Time Clock | Yes |
| Data Logger | Yes, up to 450,000 records |
| Temperature Measurement | |
| Range | -10 ~ +50°C |
| Resolution | 0.1°C |
| Accuracy | ±0.6°C |
| Humidity Measurement | |
| Range | 0 ~ 100% RH, Non-condensing |
| Resolution | 0.1% RH, Non-condensing |
| Accuracy | ±5% RH, Non-condensing |
| H2S Measurement | |
| Range | to 100 ppm (Electrochemical) |
| Resolution | 1 ppm |
| Accuracy | ±5% of measured value |
| Response Time | < 120 Sec |
| Warm-up Time | 180 Sec |
| Relay Output | |
| Channels | 1 x Form A, SPST 30 VDC @ 16 A or 250 VAC @ 16 A |
| Ethernet | |
| Ports | 10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators) |
| COM Ports | |
| Ports | 1 x RS-485 1 x Ethernet |
| Protocol | DCON and Modbus/RTU (RS-485) Modbus TCP and MQTT (Ethernet) |
| Power | |
| Consumption | Non-PoE: 1.6 W (Max.) PoE: 1.7 W (Max.) |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | Ø 150 x 53 (Ø x H) |
| Installation | Ceiling Mounting/Wall Mounting |
| Ingress Protection Rating | IP20 |
| Environment | |
| Operating Temperature | 0 ~ 50°C |
| Storage Temperature | -30 ~ +75°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Technische Daten laut Hersteller. Änderungen vorbehalten.