DNM-831I-600V-500A Voltage Attenuator and Current Transformer, 600 V / 500 A
Metal DIN-rail signal conditioner that attenuates ±600 V DC and ±500 A inputs to ±10 V for analog input modules, with 3000 VDC isolation between inputs, outputs and channels.
- Scales ±600 V DC voltage input and ±500 A current input to ±10 V outputs
- 3000 VDC isolation within the module and 3000 VDC channel-to-channel isolation
- Linear attenuation ratio with high input impedance
- Clip-type current transformer, Φ21 mm inside diameter, 1.5 m leading cable
- Includes CA-040415 cable and ASO-0001 current transformer
- Easy wiring connection in a metal DIN-rail housing
220,00 € pro Stück
| 1–9 Stück | 220,00 € | |
|---|---|---|
| 10–30 Stück | 213,00 € | −3 % |
| ab 31 Stück | 209,00 € | −5 % |
Produktinformationen "DNM-831I-600V-500A Voltage Attenuator and Current Transformer, 600 V / 500 A"
DNM-831I-600V-500A is a single-channel signal conditioner that combines a voltage attenuator and a current transformer in one metal DIN-rail housing. It scales high-voltage inputs up to ±600 V and high-current inputs up to ±500 A down to ±10 V, so they can be read by standard low-level analog input modules rather than dedicated high-power measurement hardware.
Isolation is the main reason to specify this unit. It provides 3000 VDC isolation within the module and 3000 VDC between channels, which helps keep noise from the high-voltage or high-current side away from the measurement signal. The linear attenuation ratio and high input impedance make the scaled output straightforward to interpret.
This ordering code includes the CA-040415 cable and the ASO-0001 current transformer. The current input uses a clip-type transformer with a Φ21 mm inside diameter and a 1.5 m leading cable. Other ratings in the DNM-800 series, such as the 600 V, 2000 A and 600 V, 200 A variants, are listed separately.
Applications
- High-current measurement using analog input modules such as I-7017, I-87017, M-7017RMS and I-87017W-RMS
- High-voltage measurement with isolated ±10 V analog signals
- Electrical monitoring in industrial control cabinets
| Product type: | Signal conditioner |
|---|---|
| Analog inputs: | 2 |
| Analog outputs: | 2 |
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Metal |
Technische Daten
| EMS Protection | |
|---|---|
| ESD (IEC 61000-4-2) | ±4 kV contact for power line, input and output channels, ±8 kV air for random point |
| Surge (IEC 61000-4-5) | ±3 kV for power liner |
| CT | |
| Type | Clip |
| Inside Diameter | Φ21 mm |
| Leading Cable | 1.5 m |
| Analog Input | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | High Current: ±500 A High Voltage: ±600 VDC |
| Accuracy | High Current: 1% of FSR High Voltage: 1% of FSR |
| Bandwidth | High Current: 0 ~ 50 KHz High Voltage: 20 Hz ~ 20 kHz |
| Isolation | High Current: 2.5 KV @ 50 (60) HZ/1 min |
| Analog Output | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | • High Current: ±10 VDC or 10 VAC • High Voltage: ±10 VDC or 10 VAC |
| Power | |
| Input Range | +10 VDC ~ +30 VDC |
| Consumption | 1.8 W |
| Mechanical | |
| Casing | Metal |
| Dimensions (mm) | 103 x 97 x 29 (W x L x D) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Technische Daten laut Hersteller. Änderungen vorbehalten.