Two-loop single-phase power meter with Modbus TCP over Ethernet, a 60 A clip-on CT (10 mm aperture, 1.8 m lead) and two Form A relay outputs for energy monitoring and alarms.
- True RMS voltage, current, active, reactive and apparent power with energy totals
- Single-phase, two-loop energy analysis for 1P2W systems with independent reference voltages
- Two 60 A clip-on CTs, 10 mm aperture, 1.8 m lead, measuring 0.05 A to 60 A
- Voltage input of 10 to 300 VAC
- Active power accuracy better than 0.5% at PF=1
- Two Form A power relays rated 5 A at 250 VAC or 30 VDC
204,00 € pro Stück
| 1–9 Stück | 204,00 € | |
|---|---|---|
| 10–30 Stück | 198,00 € | −3 % |
| ab 31 Stück | 194,00 € | −5 % |
Produktinformationen "PM-3112-100-MTCP Single-Phase Power Meter, 2-Loop Modbus TCP, 60 A CT"
The PM-3112-100-MTCP CR is a single-phase power meter for real-time electrical monitoring. It measures true RMS voltage and current, along with active, reactive and apparent power, energy totals, power factor and frequency, and reports the data over Modbus TCP every second.
This variant is supplied with two 60 A clip-on current transformers, each with a 10 mm aperture and a 1.8 m wire lead, so it can be fitted to existing conductors without disconnecting the load. It covers 0.05 A to 60 A on the current side and 10 to 300 VAC on the voltage side, and handles two independent loops in 1P2W configurations.
Two Form A power relay outputs, rated 5 A at 250 VAC or 30 VDC, can drive sirens, indicator lights or other alarm devices when readings cross your thresholds. The unit mounts on a DIN rail and is powered from +12 to 48 VDC.
Applications
- Generator monitoring
- Switchgear distribution systems
- Energy management
| Product type: | Power meter |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP |
| Relay outputs: | 2 |
| Ports: | 1 |
| Power input: | +12 ~ 48 VDC |
| Operating temperature: | -20 ~ +70 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Technische Daten
| AC Power Measurement | |
|---|---|
| Wiring | 1P2W-1CT |
| Loops | 1-phase: 2 |
| Input Voltage | 10 ~ 300 V |
| Input Current | PM-3112-100-MTCP: CTØ10 mm (0.05 A ~ 60 A) PM-3112-100P-MTCP: CTØ10 mm (0.05 A ~ 60 A) PM-3112-160-MTCP: CTØ16 mm (0.1 A ~ 100 A) PM-3112-160P-MTCP: CTØ16 mm (0.1 A ~ 100 A) PM-3112-240-MTCP: CTØ24 mm (0.15 A ~ 200 A) PM-3112-240P-MTCP: CTØ24 mm (0.15 A ~ 200 A) |
| Input Frequency | 50/60 Hz |
| W Accuracy | Better than 0.5% (PF=1) |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency |
| Data Update Rate | 1 Second |
| Relay Output | |
| Channels | 2 |
| Type | Power Relay |
| Contact Rating | Form A: 5 A @ 250 VAC 5 A @ 30 VDC |
| Ethernet | |
| Ports | 1x RJ45, 10/100 Base-TX |
| Protocol | Modbus TCP |
| Power | |
| Input Range | +12 ~ 48 VDC |
| Consumption | 2W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 33 x 127 x 100 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -20 ~ +70 °C |
| Storage Temperature | -25 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Technische Daten laut Hersteller. Änderungen vorbehalten.